Mitsubishi Electric was instrumental in creating a top-rated accommodation experience for guests staying beneath the stunning Remarkables mountain range.
Year-round comfort was a key part of the brief when designing the Holiday Inn Queenstown Remarkables Park Hotel. With the cold, snowy winters and hot, dry Otago summers, a safe, energy-efficient and centrally-managed comfort heating and cooling solution was required.
THE SPACE
Spread across five storeys, plus a basement, the 9,500sqm hotel features 182 rooms, a full service restaurant, bar, grab and go café, cosy media lounge, gym, four conference rooms, and a drying/storage room for all guests to keep their ski and outdoor adventure equipment. The open lobby is a particularly popular space where guests and visitors can eat, drink, work, meet, relax and socialise.

THE CHALLENGE
As a hotel project with 182 rooms, the confined sleeping spaces are classified as a Class A application under the AS/NZ 5149:2016 and therefore has a maximum charge kg for refrigerant volumes – if the system were to exceed the concentration limit, forms of mitigation such as alarms, shut off valves and ventilation would be needed to ensure greater occupant safety. Alarms as a form of mitigation can be costly in the long term.
Also, as a building with different spaces and multiple functions a mix of VRF, split systems and an air handler unit to introduce fresh air would be required for simultaneous heating and cooling to ensure comfort in every space.
However, it was important to the client that guests could soak up the view from balconies without it being interrupted by bulky outdoor air conditioning units.

THE SOLUTION
The Mitsubishi Electric R32 Hybrid advanced simultaneous heating and cooling system with heat recovery was the logical choice for accommodation areas. R32 Hybrid is based on a 2-Pipe Heat Recovery VRF System but uses water as a heat exchange medium between the Hybrid Branch Controller and the indoor units. As such, the system combines the comfort of a traditional hydronic system with the efficiency and ease of modern VRF air conditioning.
Water at the heart of the indoor units
With water rather than refrigerant used between the patented Hybrid Branch Box and the indoor units, this removed the refrigeration-containing parts from the occupied spaces by transferring heating or cooling to each indoor unit via water. R32 Hybrid not only significantly reduced the risk of refrigerant leaks in these confined spaces to safeguard guests, the total cost of the system and ongoing maintenance is reduced as the need for expensive leak detection is minimised – a major benefit for the maintenance team.
The R32 Hybrid system utilises the low GWP refrigerant R32, providing a real solution that delivers high operational efficiency while minimising the global warming potential of the refrigerants used within these systems. The hybrid technology also reduced the amount of costly refrigerant while providing additional benefits of a water-based design such as higher sensible cooling and no refrigerant noise at the indoor units.
Less material and equipment
Mitsubishi Electric’s unique 2-Pipe Heat Recovery System requires less piping than a 4-Pipe Chiller System. The system does not require an external pump, valves, sensors, actuators, or other ancillary controls associated with conventional 4-Pipe Chiller Systems.
Seamless integration for total building comfort
Due to the capacities needed, Mitsubishi Electric’s City Multi VRF was chosen for the open-plan lobby. The modular nature of the VRF system also allowed for tidy installation alongside the R32 Hybrid System and seamless integration with the air handler unit through the Zubadan Series Condenser, which introduces tempered fresh air into the kitchen.
The physical footprint required for the outdoor units on the roof top is significantly smaller than other systems. In the hotel’s public spaces, the use of discrete concealed ducted units with stylish grilles and in-ceiling cassettes allows the interior design to take centre stage.
Low-temperature heat recovery performance
The Zubadan Heat Pump outdoor unit used in conjunction with a refrigerant coil mounted in the air handler unit allows air to be pre-heated or pre-cooled prior to entering the facility to maintain safe temperatures throughout the seasons. The unique Mitsubishi Electric Zubadan Compressor in the outdoor unit ensures that full heating capacity can be provided even during the snowy Queenstown winters, with operation down to ambient temperatures of -25°C.
Centralised control
With 182 rooms to manage as well as conference rooms that can experience temperature fluctuations when hosting events, quick and remote adjustment of temperatures was key for maintenance staff. Two AE200 Centralised and Web Controller LCD touch panels were installed with three EW-50E Central Controller Expansions, allowing up to 250 indoor units to be controlled; one touch screen controls the guest rooms and the other controls common areas and back of house.
The AE200’s large, back-lit display makes programming a breeze, giving the management team control of temperature, fan speed and airflow options at the touch of a button. The ability to time room air conditioning operation with check-in and check-out times also avoids wasteful energy used when rooms are empty.

THE RESULT
As the bulk of the install was R32 Hybrid, time-consuming installation and cost-heavy ongoing leak detection requirements were avoided. Now the Holiday Inn Remarkables Park Hotel stands proud in the newly established precinct as a conveniently located one stop shop to sleep, eat and connect, in total comfort.
The client now enjoys impressive energy and operational efficiency which they can continuously monitor, make year-on-year comparisons and is a breeze for management staff to operate in response to Queenstown’s varying seasons.
Photography: IHG Hotels & Resorts and Supplied