The installation of an eight-megawatt electrode boiler to replace an inefficient six-megawatt coal-fired boiler is part of a broader energy-saving strategy at a leading wool scour in the South Island.
Supported by funding from EECA (the Energy Efficiency & Conservation Authority,) WoolWorks in Timaru has undergone a large decarbonisation project. Part of the work was completed by Piersons Refrigeration & Air Conditioning, which includes the design, supply and installation of a 750KW CO2-based heat pump.
“Traditionally, WoolWorks had used a six-megawatt coal-fired boiler to meet their hot water production needs – quite an old and inefficient process. The majority of the water is consumed by the wool scouring process, with the dirty wastewater providing an excellent opportunity to recover some waste heat,” says Matt Thomas, Managing Director at Piersons Refrigeration & Air Conditioning.
With the new system, the wastewater is collected in the common sump at approximately 35–40ºC. From this sump, the low-grade heat is transferred via an intermediate, tube-in-tube heat exchanger with a self-cleaning filtration system back into the high-temperature CO2 heat pump system where the quality of this heat is raised to 90ºC using the thermodynamic properties of a CO2-based vapour compression system.
“This high-temperature hot water is produced at a flow rate of two litres a second, with a COP of more than 3.5,” says Matthew. “This means that for every unit of electrical energy, the heat pump produces 3.5 times that amount in thermal energy.”
Piersons’ Senior Engineer, Josh Le Compte, was the supervisor for this project, and says this equipment is at the forefront of CO2-based hot water heat pump technology.
“This heat pump has been designed specifically for this project, and because of that, we’re able to extract every drop of efficiency,” says Josh.
“This heat pump was built using world-leading suppliers and with the system’s customised PLC control system, we’re able to easily commission, tune and adjust the system to match the factory’s needs. Our very user-friendly and visual human machine interface means our technicians are able to commission, diagnose and monitor all aspects of the system, and it can also be accessed remotely.”
Not only does this new system recover otherwise wasted energy for WoolWorks, it is also coupled with an Air-dryer heat reclaim unit and a flow-down heat recovery system that takes the load off the electrode boiler and allows WoolWorks to keep their power consumption under the allowable threshold.
Piersons, together with Glaciem Cooling Technologies and engineering consultant Lumen, have fully designed, built and commissioned this bespoke CO2 heat pump system. This includes the design and construction of the heat pump, pump skids, all field services and electrical, right through to the handling of the council consent.