New Zealand experiences between 50 and 80 earthquakes each day, or about 20,000 a year, with between 150 and 200 being large enough to be felt. It’s important to understand how to install HVAC equipment so it is earthquake-safe and compliant with NZS4219.
NZS4219 prevents loss of life and protects property by ensuring engineering systems in buildings are securely restrained in an earthquake.
Loss of life
NZS4219 specifies that all systems that are not structural components of the building must have restraints that transfer the load to the structure.
Restrain
Restrain all air conditioning units, heat pumps, water heaters, electrical equipment, piping and ducting, pumps, tanks and fans. Ensure it is safe and continues functioning after an earthquake.
If in doubt, shout out
If in doubt, shout out! If it is heavy or suspended, it should be restrained. If you spot any equipment (not just the items you are installing) that looks poorly restrained, shout out.
What does a safe installation look like?
- Base units, condensers, and fan coils securely bolted to the structure or on approved seismic vibration isolators
- Lateral supports in place at the top or bottom of the unit
- Condensing units that are bottom-heavy are anchored at the bottom (be aware of overturning forces)
- Proprietary system installation instructions are followed (e.g Monkey Toe, Unistrut, Boardwalk)
- Check for sway restraints on suspended equipment
- Roof-mounted equipment? Consider wind loading and weight distribution
- Fan-coils and heat pumps on a wood-framed floor or roof should be directly anchored through the cabinet on a plywood platform or wooden frame support or on approved seismic vibration isolators
Check with a structural engineer
Check with a structural engineer if in doubt! Especially where lightweight roofing is used or for custom installations. Do the installations look like they are secure? A visual inspection can be telling. Do not install condenser units on top of verandas. This is dangerous and contrary to city bylaws.
Do a seismic check now on new and existing installations. Lives depend on it. Check with your boss, architects, or structural engineers.