New regulations for air conditioners and heat pumps above 65kW
On May 1, the New Zealand Energy Efficiency (Energy Using Products) Regulations 2002 were amended to include air conditioners/heat pumps above 65kW.
Importers, manufacturers and retailers of regulated products must meet the requirements of the Energy Efficiency (Energy Using Products) Regulations. The new amendment regulations are to align the New Zealand requirements with the Australian Government’s Greenhouse and Energy Minimum Standards (Air Conditioners above 65kW) Determination 2022.
Which products are impacted?
All air conditioners/heat pumps manufactured in New Zealand, or imported from 1 May 2026, must meet the new regulatory requirements before they can be supplied. This includes meeting the Minimum Energy Performance Standards (MEPS) requirements and being registered.
MEPS applies to all air conditioners that have all of the following features:
- Use the vapour compression cycle;
- Are air-to-air;
- Have a cooling capacity or heating capacity (for heating only products) greater than 65kW;
- Are single and/or three phase;
- Are ducted and/or non-ducted;
- Are unitary or single-split or multi-split.
The air conditioner may incorporate any of the following extra features:
- Air purification;
- Ventilation;
- Heat recovery;
- Water heating;
- A heating element for air heating.
Which products are excluded?
Air conditioners/heat pumps manufactured in
New Zealand or imported prior to May 1, 2026, with a capacity above 65kW can legally be supplied without meeting these new regulatory requirements.
The following products are also excluded:
- Close control air conditioners;
- Liquid-chilling packages;
- Cooling systems that do not use a vapour compression cycle (e.g. evaporative coolers);
- Water-to-air air conditioners;
- Dehumidifiers;
- Mains-powered air conditioners specifically designed for installation in mobile applications (e.g. caravans, mobile homes, camper vans, boats and rail cars);
- Mains-powered air conditioners specifically designed for installation in specialised high temperature industrial applications (e.g. crane cabins used over blast furnaces);
- Air conditioners that do not condition air sourced from the conditioned space.
What are the MEPS requirements?
The MEPS requirements for air conditioners are minimum Annual Energy Efficiency Ratio (AEER) and Annual Coefficient of Performance (ACOP) values that the air conditioner must meet under test conditions.
The AEER for cooling is defined as the ratio of the cooling capacity (rated or tested) to the effective power input (rated or tested) for cooling and standby power. This test is conducted at an outside temperature of 35°C.
The ACOP for heating is defined as the ratio of the heating capacity (rated or tested) to the effective power input (rated or tested) for heating and standby power. This test is conducted at an outside temperature of 7°C.