Rethinking kitchen exhaust design: Airflow velocity, deposition and fire safety
Should higher airflow always mean safer ducts? Not necessarily. This article examines how deposition builds up in commercial kitchen exhaust systems, why velocity matters, and how design choices shape long-term safety and performance.
Words by Jorge Villazon-Leon
The traditional approach in dealing with the removal of commercial kitchen exhaust effluent may have assumed that the higher the airflow velocity, the greater the amount of effluent being transported through the duct and expelled to the outside. This seems a reasonable assumption. However, was there any science behind this assumption?
In duct design, the designer must achieve a balance between duct velocity and friction losses while considering noise levels. When dealing with kitchen air laden with exhaust effluent, there is also the additional aspect of deposition of material on the walls of the duct. How does airflow velocity relate to particulate matter and vapour deposition in the duct?
This is a very relevant question, considering that one of the inherent benefits of achieving lower deposition would be the reduction of potential fire risk. Are there also other aspects of duct design that could potentially yield lower deposition?
This article reviews the findings of ASHRAE research project RP-1033 which resulted in the lowering of the minimum exhaust velocity in kitchen exhaust from 7.62m/s to 2.54m/s by NFPA of United States in March 2002.
Previously Recommended Duct Velocity
Both AS1668.2-2002 and 2012 versions, recommend that discharges deemed objectionable, should be discharged to the outside at a velocity not lower than 5m/s. However, there is no recommendation in terms of airflow velocity in the duct.
The 20th edition of the Industrial Ventilation Manual for Recommended Practice by the American Conference of Governmental Industrial Hygienists (ACGIH, 1988) recommended velocity between 5.08m/s to 20.32m/s (1000 fpm to 4000 fpm). The Australian Institute of Refrigeration, Air Conditioning and Heating (AIRAH) in its Fifth Edition (AIRAH, 2013), recommended a minimum velocity of 10m/s. Until March 2002 the National Fire Protection Association of United States standard NFPA96 required a minimum velocity of 7.62m/s. Code of practice DW/172 (DW/172, 2005) recommended minimum velocities of 6 to 9m/s for main runs, 5 to 7m/s for branches and spigots.
The adoption of the above air velocities may have been based on industrial ventilation practices rather than on empirical testing.
The Research
Research project RP-1033 sponsored by ASHRAE looked at the correlation between material deposition in the duct and airflow velocity for particle matter, as well as vapour deposited on the top, bottom and both vertical walls; using the parameter ‘deposition velocity’ as the factor determining the rate at which particles are deposited on duct surfaces.
The tests were carried out using a square horizontal duct with an aspect ratio of 1:1, that is 254 mm x 254mm.
Effluent simulation conditions were created by using a mixture of oleic acid, a fluorescent dye (uranine), isopropyl alcohol and DI water. Aoleic acid is found in real cooking effluent and present in beef patties; hence it’s appropriate use.
The mixture was then injected via a jet atomiser, resulting in particle diameters of 0.49, 0.95, 1.6 and 4.3 µm. According to the research, the standard deviation σg on the particle sizes as shown in Figure 1 are values found in cooking emissions.
Four sets of tests were carried out under different conditions as follows:
• Test A: MMAD: 1.6 ± 0.2 µm (mass median aerodynamic diameters); Air Temperature: Isothermal (equal temperature); Airflow velocity: 500, 1000, 1500, 2000 fpm (2.54, 5.08, 7.62, 10.16m/s).
• Test B: MMAD: 4.3 ± 0.3 µm (mass median aerodynamic diameters); Air Temperature: Isothermal (equal temperature); Airflow velocity: 500, 1000, 1500, 2000 fpm (2.54, 5.08, 7.62, 10.16m/s).
• Test C: MMAD: 1.6 ± 0.2 µm (mass median aerodynamic diameters); Air Temperature: 120ºF (48.9ºC); Airflow velocity: 500, 1000, 1500, 2000 fpm (2.54, 5.08, 7.62, 10.16m/s); Temperature gradient: 5.9, 9.8, 10.2, 12.3ºC.
• Test D: MMAD: 1.6 ± 0.2 µm (mass median aerodynamic diameters); Air Temperature: 150ºF (65.6ºC); Airflow velocity: 500, 1000, 1500, 2000 fpm (2.54, 5.08, 7.62, 10.16m/s); Temperature gradient: 0.6, 1.9, 4.4, 5.9ºC.
Mass deposition was determined on the amount of effluent collected on stainless steel shims located inside the duct walls. Research used both constant and variable aerosol concentrations.

Implications and Important Takes from the Research Findings
1. For an isothermal process, i.e., constant temperature, there is a decrease in deposition velocity when the exhaust velocity reduces. Due to the gravitational effect, there is more deposition at the bottom of the duct as expected.
2. Temperature difference between the exhaust air and the duct walls plays an important role in deposition. This is due to hot air having more momentum and therefore migrating towards the cold. This process is called thermophoresis, also known as thermodiffusion. If ductwork is located outside in cold environments, deposition due to this mechanism will increase as well as vapour deposition. As a result, this duct would require more regular cleaning. Reducing the exhaust velocity will in this case increase temperature difference and therefore increase deposition. The obvious solution would be to insulate the duct if reduction in airflow is being considered.
3. Some exhaust systems operate at a constant airflow, although they have periods of intense cooking and other periods of light cooking. At low levels of cooking, the effluent generated will be less and therefore the effect on deposition will be considerably less. Reducing the airflow and therefore the exhaust velocity, will reduce operating costs. This can be achieved either manually or automatically. The latter by using a temperature sensor, PLC and interfacing with exhaust and make up air fans.
4. The research addresses the subject of turbulent flow. Higher exhaust velocity can induce more turbulence especially if the duct changes direction. Larger particles would have more inertia therefore unable to change direction impacting and collecting on duct walls. Thus, there is an inherent benefit of velocity reduction. In reality, a duct could have many changes of direction. However, the higher the exhaust velocity, the greater the deposition, even though vapour deposition remains unchanged. Therefore, minimising direction changes, should be considered at the design stage.
5. How relevant would duct insulation be? One of the important conclusions of this research is the fact that having an insulation rating of R-10 or greater, will in all cases reduce deposition, if exhaust velocity is reduced. It is interesting to note that vapour deposition is negligible when ducts are insulated. There are cost implications in insulating the duct, but over the life cycle of the system, there may be advantages when considering the cost of duct cleaning. Taking this a step further, the obvious question is; should standards make it compulsory for commercial kitchen exhaust ducts to be insulated?
6. Although this research brought about a lowering of standard NFAP 96 minimum exhaust velocity, it also indicated that in some cases, lowering the exhaust velocity will increase deposition. Because particle concentration is also a relevant factor, in cases where particle concentration is constant, reducing the airflow will increase particle concentration. If in this case the temperature gradient is large enough to promote the thermodiffusion effect, reducing the exhaust velocity will increase deposition. Consideration should be given to these situations.
7. When reducing the airflow, adequate capture and containment by the hood needs to be considered. Standard AS1668.2-2002 and 2012 provide prescriptive and alternative methods for determining hood airflow. Alternatively, the German VDI 2052 uses an empirical methodology, generally resulting, in lower
airflow than the prescriptive method.
8. An important consideration should be the duct aspect ratio. In some cases, space limitation is an issue. However, higher aspect ratio will increase cost (SMACNA, 1981) and surface area. A ratio of 3:1 will increase the duct area by about 15% in comparison with a ratio of 1:1. A larger area will result in greater deposition.
Conclusions
The change in minimum duct exhaust velocity by NFPA from 7.62m/s to 2.54m/s is founded on solid empirical research and provides designers
with more tools to achieve optimal design outcomes. The author is of the view that deposition is generally overlooked during the design process and that it should be treated as an integral component of the design mix. The least amount of deposition should be a design objective. The benefits are clear; a reduction in potential fire risk, and a reduction in duct cleaning costs. Although insulating the exhaust duct carries higher capital expenditure, deposition would be reduced with lower velocity.
References
ACGIH. (1988). Industrial Ventilation – A Manual of Recommended Practice (20th ed.). Ohio: American Conference of Governmental Industrial Hygienists.
AIRAH. (2013). Technical Handbook 5 Edition (5th ed.). Melbourne: The Australian Institute of Refrigeration Air Conditioning and Heating (Inc).
AS1668.2-2002. (2002). The use of ventilation and airconditioning in buildings Part2: Ventilation design for indoor air contaminants control (excluding reuirements for the health aspecs of tobacco smoke exposure) (Vol. Part 2 Ventilation design for indoor air). Sydney, Australia: Standards Australia International Ltd.
DW/172. (2005). Specifications for Kitchen Ventilation Systems. London: Heating and Ventilating Contractors’ Association.
Gerstler, W. D. (2002). New Rules For Kitchen Exhaust. ASHRAE Journal, 26-31. Retrieved from www.ashraejournal.org
NFPA 96. (2014). Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. Chicago: National Fire Protection Association.
SMACNA. (1981). HVAC Systems Duct Design. Virginia: Sheet Metal and Air Conditioning Contractors’ National Association Inc.
About the Author: Jorge Villazon-Leon has been involved in the HVAC industry for over 35 years in New Zealand and overseas and is a long time member of IRHACE. He has written two previous technical papers for the IRHACE Journal and was awarded recognition in 2012 for the year’s best article. He is general manager of Air & Odour Management New Zealand specialising in commercial kitchen exhaust.